Functions
7.10 Safe Torque Off (STO) safety function
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
227
Function table
Fill in the following table for your machine.
Mode of operation Safety device Drive Controlling the safety
function
Status of the safety
function
Table 7- 40 Example:
Mode of operation Safety device Drive Controlling the safety
function
Status of the safety
function
Protective door closed and
locked
1
2
-
-
not active
not active
Production
Protective door unlocked 1
2
F-DI 0
PROFIsafe
STO active
STO active
Protective door closed and
locked
1
2
-
PROFIsafe
not active
STO active
Setup
Protective door unlocked 1
2
F-DI 0
PROFIsafe
STO active
STO active
The following is checked during the function test:
The hardware is functioning properly.
The digital inputs of the inverter are assigned correctly for the safety function.
The PROFIsafe address of the inverter is set correctly.
The safety function is parameterized correctly.
Routine for forced dormant error detection of the switch-off signal paths on the Control
Unit.
Note
Perform the acceptance test with the maximum possible speed and acceleration.
Procedure
Table 7- 41 "Safe Torque Off" (STO) function
No. Description Status
Initial state:
The inverter is in "Ready" state (p0010 = 0).
The inverter indicates neither faults nor alarms for safety functions (r0945, r2122, r2132).
1.
STO is not active.