5.8 Status word messages
Status word messages (MELDW)
Table 5-13 Status word for messages and interconnection with parameters in the converter
Bit Meaning Description P No.
0 0 = Ramp-function generator active The motor is presently acceler‐
ating or braking
p2082[0] = r2199.5
1 = Ramp-up/ramp-down completed Speed setpoint and actual
speed are the same.
1 1 = Torque utilization [%] < torque threshold value 2
(p2194)
--- p2082[1] = r2199.11
2 1 = |n_act| < speed threshold value 3 (p2161) --- p2082[2] = r2199.0
3 1 = |n_act| speed threshold value 2 (p2155) --- p2082[3] = r2197.1
4, 5 Reserved
6 1 = No motor overtemperature alarm The motor temperature is with‐
in the permissible range.
p2082[6] = r2135.14
7 1 = No alarm, thermal power unit overload The converter temperature is
within the permissible range.
p2082[7] = r2135.15
8 1 = Speed setpoint - actual value deviation within toler‐
ance t_on
Speed setpoint and actual
speed are within the permissi‐
ble tolerance range p2163.
p2082[8] = r2199.4
9, 10 Reserved
11 1 = Controller enable The speed controller is enabled. p2082[11] = r0899.8
12 1 = Drive ready The converter is ready to be
switched on.
p2082[12] = r0899.7
13 1 = Pulses enabled The motor is switched on. p2082[13] = r0899.11
14, 15 Reserved