What to do if Siemens DC Drives show alarm A01028?
M
Michele GuerreroSep 2, 2025
If alarm A01028 appears, it indicates that the parameterization on the memory card was created with a different type of module (order number, MLFB). Therefore, check the module parameters and recommission if necessary.
R
Richard SantiagoSep 3, 2025
What to do if Siemens DC Drives display fault F01659?
N
Nicole HoganSep 3, 2025
If fault F01659 occurs, the converter should be reset to the factory setting. Resetting the safety functions is not allowed when they are enabled. To resolve this, follow these steps: p0010 = 30 (Parameter reset); p9761 = … (Enter password for the safety functions); p0970 = 5 (Reset Start Safety Parameter). The converter sets p0970 = 5 after resetting the parameters. Then, reset the converter to the factory setting again.
T
torresericSep 3, 2025
What to do if Siemens DC Drives display alarm A07015?
E
elizabethmoralesSep 3, 2025
If alarm A07015 is triggered, check that the sensor is connected correctly and verify the parameter assignment (p0601).
P
Paula JonesSep 4, 2025
What to do if Siemens DC Drives display fault F01033?
B
Barbara EllisSep 4, 2025
If fault F01033 occurs, set the value of the reference parameter to a value other than 0.0 (p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).
J
Jason StephensSep 4, 2025
What to do if Siemens DC Drives display fault F01034?
I
ihernandezSep 4, 2025
If fault F01034 occurs, select the value of the reference parameter so that the parameters involved can be calculated in the per unit notation (p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).
H
Heidi WardSep 4, 2025
What to do if Siemens DC Drives display fault F03505?
N
navarrojasonSep 5, 2025
If fault F03505 is displayed, check the connection to the signal source for interrupts and verify the level of the signal supplied. The input current measured by the analog input can be read out in r0752.
M
Mark JohnsonSep 5, 2025
What to do if Siemens DC Drives display alarm A03520?
J
jeffrey37Sep 5, 2025
If alarm A03520 appears, check that the sensor is connected correctly.
M
Michael LittleSep 5, 2025
What to do if Siemens DC Drives display fault F01122?
E
ecantuSep 6, 2025
If fault F01122 appears, reduce the frequency of the pulses at the probe input.
T
Tammy MooreSep 6, 2025
What to do if Siemens DC Drives display fault F01600?
R
Rachael WagnerSep 6, 2025
If fault F01600 occurs, select STO and then deselect it again.
S
Sean StevensSep 6, 2025
What to do if Siemens DC Drives display fault F01650?
C
Cindy SimonSep 7, 2025
If fault F01650 is displayed, carry out an acceptance test and create a test certificate. Then, switch the Control Unit off and then on again.
Siemens SINAMICS G120C Specifications
General
Communication Interfaces
PROFINET, PROFIBUS, USS, Modbus RTU
Protection Class
IP20
Ambient Temperature
-10°C to +50°C
Storage Temperature
-40°C to +70°C
Power Range
0.55 kW to 132 kW
Voltage Range
380 V to 480 V
Output Voltage
0 V to Supply Voltage
Frequency Range
0 Hz to rated output frequency
Control Modes
Vector control with encoder
Protection
Overload, overvoltage, undervoltage, short circuit, ground fault