Accessories
9.2 Mounting frames for PT power modules
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
107
9.2
Mounting frames for PT power modules
Order numbers for mounting frames
FSA: 6SL3260-6AA00-0DA0
FSB: 6SL3260-6AB00-0DA0
FSC: 6SL3260-6AC00-0DA0
All of the necessary nuts and seals are included in the scope of delivery.
Mounting instructions for the mounting frames
Procedure
Proceed as follows to correctly mount the Power Module:
1. Prepare a cutout and holes in the control cabinet panel for the mounting frame
corresponding to the dimension drawing.
2. Insert the mounting frame from the rear of the control cabinet through the corresponding
holes and fix it in place at the fixing screws for the control cabinet panel; tighten the two
nuts by hand.
3. Attach the seal to the inner side of the control cabinet.
4. Insert the Power Module and tighten the screws by hand.
5. Finally, tighten the eight or ten screws with a torque of 3.5 Nm.
You have correctly installed the Power Module.