Technical data
7.2 Ambient conditions
Power Module PM240-2
66 Hardware Installation Manual, 01/2017, A5E33294624B AE
Ambient conditions for transport in the transport packaging
Climatic ambient conditions - 40° C … + 70° C, according to Class 2K4 to EN 60721-3-2
maximum humidity 95% at 40° C
Mechanical ambient condi-
tions
• FSA … FSC: Shock and vibration permissible according to 1M2 to EN 60721-3-2
• FSD … FSF: Shock and vibration permissible according to 2M3 to EN 60721-3-2
Protection against chemical
Protected according to Class 2C2 to EN 60721-3-2
Biological ambient condi-
Suitable according to Class 2B1 to EN 60721-3-2
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions
- 25° C … + 55° C, according to Class 1K3 to EN 60721-3-1
Protection against chemical
Protected according to Class 1C2 to EN 60721-3-1
Biological ambient condi-
Suitable according to class 1B1 to EN 60721-3-1
Ambient conditions in operation
Installation altitude Up to 1000 m above sea level without limitations
Restrictions for special ambient conditions (Page 93)
Climatic ambient conditions
1)
• FSA ... FSC ambient operating temperature
2)
– For operation according to Low Overload: -10° C … +40° C
– For operation according to High Overload: -10° C … +50° C
–
Restrictions for special ambient conditions (Page 93)
• FSD ... FSF ambient operating temperature
2)
– For operation according to Low Overload: -20° C … +40° C
– For operation according to High Overload: -20° C … +50° C
–
Restrictions for special ambient conditions (Page 93)
• Relative humidity: 5 … 95%, condensation not permitted
• Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
Mechanical ambient condi-
tions
Shock and vibration permissible, according to Class 3M1 to EN 60721-3-3
Vibration test during operation according to IEC 60068-2-6 Test Fc (sinusoidal)
• 0 ... 57 Hz: 0.075 mm deflection amplitude
• 57 ... 150 Hz: 1 g acceleration amplitude
• 10 frequency cycles per axis
Shock test according to IEC 60068-2-27 Test Ea (half-sine)
• 5 g peak acceleration
• 30 ms duration
• 3 shocks in all three axes in both directions