Connecting-up
5.2 Connecting the line and motor cable at the inverter
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
53
Table 5- 3 Permissible cable lengths for the motor connection, FSF
with or without filter, with or
without output reactor
without filter, with two output
reactors in series
1)
Connection terminals at the inverter
Table 5- 4 Connection, cross-section and tightening torque for PM240-2 Power Modules
Cross-section, tightening torque
Stripped
insulation
length
Line supply, motor,
DC link and braking
resistor
Plug connector
with screw termi-
2
2
6 …16 mm², 1.3 Nm 10 … 6 AWG, 12 lbf in 10 mm
Line supply, motor
and DC link
Screw-type termi-
nal
10 … 35 mm
2
,
2.5 … 4.5 Nm
20 … 10 AWG, 22 lbf in
18 mm
Braking resistor 2.5 … 16 mm
2
,
20 … 6 AWG, 15 lbf in 10 mm
Line supply, motor
Screw-type termi-
nal
25 … 70 mm
2
, 8 … 10 Nm 6 … 3/0 AWG,
25 mm
Braking resistor 10 … 35 mm
2
,
2.5 … 4.5 Nm
20 … 10 AWG, 22 lbf in
18 mm
Line supply, motor
and DC link
Cable lug accord-
35 … 2 × 120 mm
2
,
22 … 25 Nm
1 … 2 × 4/0 AWG,
210 lbf.in
--
Braking resistor Screw-type termi-
25 … 70 mm
2
, 8 … 10 Nm 6 … 3/0 AWG,
25 mm