3.1 Component specification according to UL
Power Module PM240-2
20 Hardware Installation Manual, 01/2017, A5E33294624B AE
3.1
Component specification according to UL
The inverters have UL approval according to UL508C and CSA C22.2 No. 274-13.
Further information and a link for downloading the appropriate certificates can be found in
the following Section:
Directives and standards (Page 137)
3.2
Permissible motors
Note
Motors for inverter operation
Only use motors that are suitable for operation with inverters with a DC link.
Motors for 200 V Power Modules
For the 200 V Power Modules, induction motors are permissible in the range from
25%150% of the inverter power without any restrictions.
Motors for 400 V Power Modules
For the 400 V Power Modules, induction motors are permissible in the range from
25 % … 150 % of the inverter power without any restrictions.
Motors for 690 V Power Modules
For the 690 V Power Modules, induction motors are permissible in the range from 50
% … 150 % of the inverter power without any restrictions.