Technical data
7.7 Technical data, 690 V inverters
Power Module PM240-2
88 Hardware Installation Manual, 01/2017, A5E33294624B AE
Technical data, 690 V inverters
Motors for 690 V Power Modules
For the 690 V Power Modules, induction motors are permissible in the range from 50
% … 150 % of the inverter power without any restrictions.
Note
Motors for inverter operation
Only use motors that are suitable for operation with inverters with a DC link.
General data, 690 V inverters
Line voltage
• for systems according to IEC: 3-ph. AC 500 V … 690 V ± 10% (in operation -20% < 1 min)
• for systems according to UL 3-ph. AC 500 V … 600 V ± 10% (in operation -20% < 1 min)
filtered devices only with Slash Rating (600Y/347V AC)
Line supply configurations
Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 44)
3-ph. AC 0 V … 0.95 x input voltage (max.)
0 … 550 Hz, depending on the control mode
< LO base load input current
Overvoltage category
according to EN 61800-5-
III for line supplies
Pulse frequency 2 kHz (factory setting), can be adjusted to 4 kHz
If you increase the pulse frequency, the inverter reduces the maximum output current.
Short-circuit current rating
(SCCR) and branch pro-
tection
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Braking methods DC braking, compound braking, dynamic braking with integrated braking chopper
Degree of protection ac-
IP20; must be installed in a control cabinet
Protection class according
The inverters are devices with protection class I
Touch protection accord-
DGUV regulation 3 when used for the intended purpose
Cooling in compliance
Forced air cooling AF