Connecting-up
5.1 Permissible line supplies
Power Module PM240-2
46 Hardware Installation Manual, 01/2017, A5E33294624B AE
5.1.3
IT system
In an IT line system, all of the conductors are
insulated
with respect to the PE protective
conductor
or connected to the PE protec-
tive conductor through an impedance.
There are IT systems with and without tran
s-
fer of the neutral conductor N.
Inverter operated on an IT line system
Inverters with integrated line filter:
Operation on IT line systems not permissible.
Inverter without line filter:
Operation on all IT line systems permissible.
Behavior of the inverter when a ground fault occurs
In some instances, even for a ground fault, the inverter should still remain functional. In
cases such as these, you must install an output reactor. This prevents an overcurrent trip or
damage to the drive.