Loading...
Connecting-up
5.1 Permissible line supplies
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
45
5.1.2
TT line system
In a TT line system, the transformer groun
d-
ing and the installation grounding are in
de-
pendent of one another.
There are TT line supplies where the neutral
conductor N is either transferred
or not.
Inverter operated on a TT line system
Inverter with integrated or external line filter:
Operation on TT line systems with grounded neutral point permissible.
Operation on TT line systems without grounded neutral point not permissible.
Inverter without line filter:
Operation on all TT line systems permissible.
For installations in compliance with IEC, operation on a TT line system is permissible. For
installations in compliance with UL, operation on a TT line system is not permissible.