Technical data
7.8 Restrictions for special ambient conditions
Power Module PM240-2
94 Hardware Installation Manual, 01/2017, A5E33294624B AE
Current reduction as a function of the installation altitude and ambient temperature
At installation altitudes above 1000 m and temperatures higher than 40° C (low overload) or
50° C (high overload), the inverter output current is reduced. The following tables contain the
details.
Table 7- 30 Maximum permitted output current for loading according to LO
Installation
altitude [m]
up to
Output current in [%] when loading to LO
100 95 88 81 72 63
Table 7- 31 Maximum permitted output current when loading according to HO
Installation
altitude [m]
up to
Output current in [%] when loading to HO
Also observe the maximum permissible ambient operating temperatures for the Control Unit
and possibly the Operator Panel.