Commissioning
4.19 Commissioning functions
Hydraulic Drive
System Manual, 04/2015, 6SL3097-4BA00-0BP1
123
Hydraulic/electrical interpolation
Objective
Contour precision is achieved with a drive dynamic response, which is set the same for all of
the axes involved. The statement applies to both hydraulic and electric drives.
In addition to identical K
v
settings, it must be ensured that the step response of the velocity
controller is "identical".
A velocity setpoint filter of the faster axis (e.g. electric) must be set to the difference between
the time constants of the velocity control loop (T
v, ers
)
T
filter , el
= T
ers, hyd
- T
ers, el
Figure 4-46 Hydraulic/electrical interpolation
When dynamic servo control (DSC) is active, the DSC function must be activated on all
interpolating axes.
The following commissioning functions are available for HLA drives:
● Measuring function (Page 124)
● Function generator (Page 132)
● Circularity test (Page 136)
● Trace (Page 137)