Commissioning
4.13 Configuration - BICO interconnection
Hydraulic Drive
System Manual, 04/2015, 6SL3097-4BA00-0BP1
69
BICO interconnection for 2nd OFF2
The 2nd OFF2 signal of this drive can be wired to one of the terminals in the selection list.
When selecting, a distinction is made as to whether the drive is connected to a Control Unit
or an NX. For a Control Unit, connection can be made to terminal block X132 and for an NX
expansion module, connection can be made to terminal block X122.
If you select a terminal that is already linked with another drive, then the following options
are available:
● "Replace available terminal assignment by the drive"
The terminal assignment already existing on this terminal is removed in other drives. A
new terminal assignment is established to this drive alone.
● "Add drive of the existing terminal assignment"
The new assignment to this terminal is established in addition to the already existing
terminal assignments for this drive.