Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
203
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data set
Data
type
Acc.
Level
r0038
CO: Filtered power
factor
- - - - - Float 3
Displays the filtered power factor.
r0039
CO: Energy con-
sumpt. meter [kWh]
- - - - - Float 2
Displays electrical energy used by converter since display was last reset (see P0040 - reset energy con-
sumption meter).
Dependency:
Value is reset when P0040 = 1 (reset energy consumption meter).
P0040
Reset energy con-
sumpt. and energy
saved meter
0 - 1 0 T - - U16 2
Resets value of r0039 (energy consumption meter) and r0043 (energy saved meter) to zero.
0
No reset
1
Reset r0039 to 0
P0042[0...1]
Energy saving scaling
0.000 - 100.00
0.000
T
-
-
Float
2
Scales the calculated energy saved value
Index:
[0]
Factor for kWh to currency conversion
[1]
Factor for kWh to CO2 conversion
r0043[0...2]
Energy saved [kWh]
-
-
-
-
-
Float
2
Displays calculated energy saved
Index:
[0]
Energy saving in kWh
[1]
Energy saving in currency
[2]
Energy saving in CO2
r0050
CO/BO: Active com-
mand data set
- - - - - U16 2
Displays currently active command data set.
0
Command data set 0 (CDS)
1
Command data set 1 (CDS)
2
Command data set 2 (CDS)
Note:
See P0810
r0051[0...1]
CO: Active drive data
set (DDS)
- - - - - U16 2
Displays currently selected and active drive data set (DDS).
0
Drive data set 0 (DDS0)
1
Drive data set 1 (DDS1)
2
Drive data set 2 (DDS2)
Index:
[0]
Selected drive data set
[1]
Active drive data set
Note:
See P0820

Table of Contents