Parameter list
8.2 Parameter list
SINAMICS V20 Converter
204 Operating Instructions, 10/2019, A5E34559884-012
r0052.0...15
CO/BO: Active status
word 1
- - - - - U16 2
Displays first active status word of converter (bit format) and can be used to diagnose converter status.
Deviation setpoint/act. value
Warning: Motor current/torque limit
r0052 bit 03 "Converter fault active": Output of bit 3 (Fault) will be inverted on digital output (Low = Fault, High = No
Fault);
r0052 bit 06 "On inhibit" is active with OFF2 or OFF3 and becomes disabled with OFF1, NOT OFF2 and NOT OFF3.
r0053.0...11
CO/BO: Active status
word 2
- - - - - U16 2
Displays second status word of converter (in bit format).
Act. current |r0068| >= P2170
f_act >= setpoint (f_set)
10 PID output r2294 == P2292 (PID_min) Yes No
PID output r2294 == P2291 (PID_max)
r0053 bit 00 "DC brake active" ==> see P1233