Allows ON/OFF1 reverse command source to be selected using BICO. In general a positive frequency
setpoint is run up counterclockwise (negative frequency).
P0843[0...2] BI: ON/OFF2 0 - 4294967295 1 T - CDS U32/B
3
Allows ON/OFF2 command source to be selected using BICO. The default setting 1.0 will disable this
For digital inputs as command source BICO requires P0700 set to 2 (enable BICO). If one of the digital
inputs is selected for ON/OFF2, the converter will not run unless the digital input is active. OFF2 means
immediate pulse-disabling; the motor is coasting. OFF2 is low-active, i.e. :0 = Pulse disabling. 1 = Pulses
enabled. (As long as there are no other OFF conditions active).
The ON/OFF2 functionality is not supported in 2/3 wire modes. Do not select ON/OFF2 unless P0727 = 0.
Defines first source of OFF2 when P0719 = 0 (BICO).
If one of the digital inputs is selected for OFF2, the converter will not run unless the digital input is active.
OFF2 means immediate pulse-disabling; the motor is coasting. OFF2 is low-active, i.e.:
0 = Pulse disabling.
Defines second source of OFF2.
In contrast to P0844 (first source of OFF2), this parameter is always active, independent of P0719 (selec-
tion of command and frequency setpoint). See P0844.
Defines first source of OFF3 when P0719 = 0 (BICO).
If one of the digital inputs is selected for OFF3, the converter will not run unless the digital input is active.
OFF3 means quick ramp-down to 0.
OFF3 is low-active, i.e.
0 = Quick ramp-down.
Defines second source of OFF3.
In contrast to P0848 (first source of OFF3), this parameter is always active, independent of P0719 (selec-
tion of command and frequency setpoint). See P0848.
Defines source of pulse enable/disable signal.
Active only when P0719 = 0 (Auto selection of command/setpoint source).