Parameter list
8.2 Parameter list
SINAMICS V20 Converter
246 Operating Instructions, 10/2019, A5E34559884-012
Defines fixed frequency setpoint 1. There are 2 types of fixed frequencies:
• Direct selection (P1016 = 1):
– In this mode, 1 fixed frequency selector (P1020 to P1023) selects 1 fixed frequency (P1001 to
P1004).
– If several inputs are active together, the selected frequencies are summed.
Example: fixed frequency 1 (P1001) + fixed frequency 2 (P1002) + fixed frequency 3 (P1003) +
fixed frequency 4 (P1004).
• Binary coded selection (P1016 = 2):
– Up to 16 different fixed frequency values can be selected using this method.
See P1020 to P1023 for assigning desired digital inputs to the fixed frequency bits.
Select fixed frequency operation (using P1000).
Converter requires ON command to start in the case of direct selection. Therefore r1025 must be con-
nected to P0840 to start.
Fixed frequencies can be selected using the digital inputs.