Parameter list
8.2 Parameter list
SINAMICS V20 Converter
252 Operating Instructions, 10/2019, A5E34559884-012
Defines source of main setpoint.
Motor potentiometer (MOP) setpoint
CI: Main setpoint scaling
Defines source of the main setpoint scaling.
P1074[0...2]
BI: Disable additional
setpoint
0 - 4294967295 0 U, T - CDS U32 3
Disables additional setpoint.
Defines source of the additional setpoint (to be added to main setpoint).
P1076[0...2]
CI: Additional setpoint
scaling
0 - 4294967295 [0] 1
[1] 0
T 4000H CDS U32 3
Defines source of scaling for additional setpoint (to be added to main setpoint).
r1078
CO: Total frequency
setpoint [Hz]
- - - - - Float 3
Displays sum of main and additional setpoints.
r1079
CO: Selected frequency
setpoint [Hz]
- - - - - Float 3
Displays selected frequency setpoint. Following frequency setpoints are displayed:
• r1078 Total frequency setpoint
• P1058 JOG frequency right
• P1059 JOG frequency left
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The minimum
frequency P1080 represents a masking frequency of 0 Hz for all frequency target value sources e.g. ana-
log input, MOP, FF, USS with the exception of the JOG target value source (analogous to P1091). Thus
the frequency band +/-P1080 is run through in optimum time by means of the acceleration/deceleration
ramps. Dwelling in the frequency band is not possible. Furthermore, an overshoot of the actual frequency
f_act upper minimum frequency P1080 is output by the signal function |f_act| > f_min.
Value set here is valid both for clockwise and for counterclockwise rotation.
Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.