Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
253
Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value
set here is valid for both clockwise and counterclockwise rotation.
Furthermore, the monitoring function |f_act| >= P1082 (r0052 bit 10, see example below) is affected by
The maximum value of P1082 also depends on the nominal frequency: Max. P1082 = min (15*P0310,
550.0 Hz). As consequence P1082 can be affected if P0310 is changed to a smaller value. The maximum
frequency and the pulse frequency depending on each other. The maximum frequency affects the pulse
frequency according to the following table.
max
Example:
If P1082 is set to 350 Hz a pulse frequency from at least 6 kHz is necessary. If P1800 is smaller than 6
kHz the parameter is changed P1800 = 6 kHz.
The maximum output frequency of converter can be exceeded if one of the following is active:
When using the setpoint source
• Analog Input
• USS
the setpoint frequency (in Hz) is cyclically calculated using
• a percentage value(e.g. for the analog input r0754)
• a hexadecimal value (e.g. for the USS r2018[1])
• and the reference frequency P2000.
If for example P1082 = 80 Hz, P2000 = 50 Hz and the analog input is parameterized with P0757 = 0 V,
P0758 = 0 %, P0759 = 10 V, P0760 = 100 %, a setpoint frequency of 50 Hz will be applied at 10 V of the
analog input. When Quick Commissioning is carried out P2000 is changed as follows: P2000 = P1082.