Parameter list   
8.2 Parameter list 
  SINAMICS V20 Converter 
278  Operating Instructions, 10/2019, A5E34559884-012 
  If a BICO connection is made between two parameters or alternatively using P0719 or P1000, the 'unit' of 
the parameters (standardized (Hex) or physical (i.e. Hz) values) may differ. SINAMICS implicitly makes an 
automatic conversion to the target value. 
 
When Quick Commissioning is carried out, P2000 is changed as follows: P2000 = P1082. 
  P2000 represents the reference frequency of the above mentioned interfaces. 
A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface. 
Unlike P1082 (Maximum Frequency) this limits the converter frequency internally independent of the ref-
erence frequency. 
By modification of P2000 it will also adapt the parameter to the new settings. 
 
  Reference parameters are intended as an aid to presenting setpoint and actual value signals in a uniform 
manner. 
This also applies to fixed settings entered as a percentage. 
A value of 100 % corresponds to a process data value of 4000H, or 4000 0000H in the case of double 
values. 
In this respect, the following parameters are available: 
 
Changes to P2000 result in a new calculation of P2004.