Parameter list
8.2 Parameter list
SINAMICS V20 Converter
280 Operating Instructions, 10/2019, A5E34559884-012
Sets baud rate for USS/MODBUS communication.
7 19200 bps
Before fitting SINAMICS V20 Smart Access to V20, if RS485 communication is present, then you must set
P2010[1] = 12 via the BOP.
This parameter, index 0, will alter the baudrate on RS485 regardless of the protocol selected in P2023.
Sets unique address for converter.
You can connect up to a further 30 converters via the serial link (i.e. 31 converters in total) and control
them with the USS serial bus protocol.
Defines the number of 16-bit words in PZD part of USS telegram. In this area, process data (PZD) are
continually exchanged between the master and slaves. The PZD part of the USS telegram is used for the
main setpoint, and to control the converter.
USS protocol consists of PZD and PKW which can be changed by the user via P2012 and P2013 respec-
tively.