Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
287
Sets unique address for converter.
Modbus reply timeout [ms]
The time in which the converter is allowed to respond to the Modbus master. If the forming of a response
needs more time than specified in this parameter, the processing is done, but no response is sent.
Select the protocol which runs on the RS485 link.
After changing P2023, powercycle the converter. During the powercycle, wait until LED has gone off or
the display has gone blank (may take a few seconds) before re-applying power. If P2023 has been
changed via a PLC, make sure the change has been saved to EEPROM via P0971.
r2024[0...1]
USS/MODBUS error-free
telegrams
- - - - - U16 3
Displays number of error-free USS/MODBUS telegrams received.
The state of the telegram information on RS485 is reported regardless of the protocol set in P2023.
r2025[0...1]
USS/MODBUS rejected
telegrams
- - - - - U16 3
Displays number of USS/MODBUS telegrams rejected.
See r2024
r2026[0...1]
USS/MODBUS character
frame error
- - - - - U16 3
Displays number of USS/MODBUS character frame errors.
r2027[0...1]
- - - - - U16 3
Displays number of USS/MODBUS with overrun error.
r2028[0...1]
- - - - - U16 3
Displays number of USS/MODBUS telegrams with parity error.
Displays number of USS telegrams with unidentified start.