Parameter list   
8.2 Parameter list 
  SINAMICS V20 Converter 
288  Operating Instructions, 10/2019, A5E34559884-012 
r2030[0...1] 
-  -  -  -  -  U16  3 
Displays number of USS/MODBUS telegrams with BCC/CRC error. 
Displays number of USS/MODBUS telegrams with incorrect length. 
Parity of MODBUS telegrams on RS485. 
Also see P2010 for baudrate and P2035 for stop bit settings. You must set P2034 to 0 if P2035=2. 
P2035 
MODBUS stop bits on 
RS485 
1 - 2  1  U, T  -  -  U16  2 
Number of stop bits in MODBUS telegrams on RS485. 
Also see P2010 for baudrate and P2034 for parity settings. You must set P2035 to 2 if P2034=0. 
r2036.0...15  
BO: CtrlWrd1 from 
USS/MODBUS on RS485 
-  -  -  -  -  U16  3 
  Displays control word 1 from USS/MODBUS on RS485 (i.e. word 1 within USS/MODBUS = PZD1). See 
r0054 for the bit field description. 
r2037.0...15  
BO: CtrlWrd2 from USS 
on RS485 (USS) 
-  -  -  -  -  U16  3 
  Displays control word 2 from USS on RS485 (i.e. word 4 within USS = PZD4). See r0055 for the bit field 
  To enable the external fault (r2037 bit 13) facility via USS, the following parameters must be set: 
•  P2012 = 4 
•  P2106 = 1