Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
289
r2053[0...7]
I/O Extension Module
identification
- 0 - - - U16 3
Displays identification data of the I/O Extension Module.
I/O Extension Module ID number
I/O Extension Module firmware version number (major)
I/O Extension Module firmware version number (minor)
I/O Extension Module firmware version number (hot fix)
I/O Extension Module firmware version number (internal)
Company ID (Siemens = 42)
r2067.0...12
CO/BO: Digital input
values status
- - - - - U16 3
Displays status of digital inputs.
This is used for BICO connection without software intervention.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
Selects up to 3 faults or alarms for non-default reactions.
If, for example, an OFF3 is to be carried out instead of an OFF2 for a fault, the fault number has to be
entered in P2100 and the desired reaction selected in P2101 (in this case (OFF3) P2101 = 3).
All fault codes have a default reaction to OFF2.
Only the following faults (F11,F12,F20,F35,F71,F72,F85,F200,F221,F222, and F452) can be changed
from the default reactions.