Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
289
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
r2053[0...7]
I/O Extension Module
identification
- 0 - - - U16 3
Displays identification data of the I/O Extension Module.
Index:
[0]
I/O Extension Module ID number
[1]
I/O Extension Module firmware version number (major)
[2]
I/O Extension Module firmware version number (minor)
[3]
I/O Extension Module firmware version number (hot fix)
[4]
I/O Extension Module firmware version number (internal)
[5]
Not used
[6]
Not used
[7]
Company ID (Siemens = 42)
r2067.0...12
CO/BO: Digital input
values status
- - - - - U16 3
Displays status of digital inputs.
Bit
Signal name
1 signal
0 signal
00
Digital input 1
Yes
No
01
Digital input 2
Yes
No
02
Digital input 3
Yes
No
03
Digital input 4
Yes
No
04
Digital input 5
Yes
No
05
Digital input 6
Yes
No
11
Digital input AI1
Yes
No
12
Digital input AI2
Yes
No
Note:
This is used for BICO connection without software intervention.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
P2100[0...2]
Alarm number selection
0 - 65535
0
T
-
-
U16
3
Selects up to 3 faults or alarms for non-default reactions.
Example:
If, for example, an OFF3 is to be carried out instead of an OFF2 for a fault, the fault number has to be
entered in P2100 and the desired reaction selected in P2101 (in this case (OFF3) P2101 = 3).
Index:
[0]
Fault Number 1
[1]
Fault Number 2
[2]
Fault Number 3
Note:
All fault codes have a default reaction to OFF2.
Only the following faults (F11,F12,F20,F35,F71,F72,F85,F200,F221,F222, and F452) can be changed
from the default reactions.