Parameter list
8.2 Parameter list
SINAMICS V20 Converter
290 Operating Instructions, 10/2019, A5E34559884-012
Sets converter stop reaction values for faults selected by P2100 (alarm number selection). This indexed
parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
1 OFF1 stop reaction
No reaction, warning only
Settings 1 - 3 are only available for fault codes.
Setting 4 is only available for warnings.
Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103[0...2]
BI: 1. Faults acknowl-
edgement
0 - 4294967295 722.2 T - CDS U32 3
Defines first source of fault acknowledgement.
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
P2104[0...2]
BI: 2. Faults acknowl-
edgement
0 - 4294967295 0 T - CDS U32 3
Selects second source of fault acknowledgement.
See P2103
Selects source of external faults.
Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be
Recent Warnings --, warning 1
Recent Warnings --, warning 2
Recent Warnings -1, warning 3
Recent Warnings -1, warning 4
Indices 0 and 1 are not stored.
The LED indicates the warning status in this case. The keypad will flash while a warning is active.
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.