Parameter list
8.2 Parameter list
SINAMICS V20 Converter
330 Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P3853[0...2]
Frost protection frequency
[Hz]
0.00 - 550.00 5.00 U, T - DDS Float 2
The frequency applied to the motor when frost protection is active.
Dependency:
See also P3852.
P3854[0...2]
Condensation protection
current [%]
0 - 250 100 U, T - DDS U16 2
The DC current (as a percentage of nominal current) which is applied to the motor when condensation
protection is active.
Dependency:
See also P3852.
P3900
End of quick commis-
sioning
0 - 3 0 C(1) - - U16 1
Performs calculations necessary for optimized motor operation. After completion of calculation, P3900 and
P0010 (parameter groups for commissioning) are automatically reset to their original value 0.
0
No quick commissioning
1
End quick commissioning with factory reset
2
End quick commissioning
3
End quick commissioning and initiate motor data calculation
Dependency:
Changeable only when P0010 = 1 (quick commissioning).
Note:
P3900 = 1:
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick
commissioning" are retained; all other parameter changes, including the I/O settings, are lost. Motor calcu-
lations are also performed.
P3900 = 2:
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning
menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the
motor calculations performed.
P3900 = 3:
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commis-
sioning with this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (motor
weight), P0350 (stator resistance), P2000 (reference frequency), P2002 (reference current).
When transferring P3900, the converter uses its processor to carry out internal calculations.
Communications - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to
make these calculations. This can result in the following error messages at the connected SIMATIC S7
control (communications via Fieldbus):
Parameter fault 30
Converter fault 70
Converter fault 75
r3930[0...4]
Converter data version
-
-
-
-
-
U16
3
Displays the A5E number and the converter data versions.
Index:
[0]
A5E 1st 4 digits
[1]
A5E 2nd 4 digits
[2]
Logistic Version
[3]
Fixed Data Version
[4]
Calib Data Version