Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
331
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P3950
Access of hidden pa-
rameters
0 - 255 0 U, T - - U16 4
Accesses special parameters for development (expert only) and factory functionality (calibration parame-
ter).
r3954[0...12]
CM info and GUI ID
-
-
-
-
-
U16
4
Used to classify firmware (only for SIEMENS internal purposes).
Index:
[0]
CM label (increment/branch)
[1]
CM label (counter)
[2]
CM label
[3...10]
GUI ID
[11]
GUI ID major release
[12]
GUI ID minor release
r3978
BICO counter
-
-
-
-
-
U32
4
Counts the number of changed BICO links.
P3981
Reset active fault
0 - 1
0
T
-
-
U16
4
Resets active faults when changed from 0 to 1.
0
No fault reset
1
Reset fault
Note:
See P0947 (last fault code)
Automatically reset to 0.
P3984
Client telegram off time
[ms]
100 - 10000 1000 T - - U16 3
Defines time after which a fault will be generated (F73) if no telegram is received from the client.
Dependency:
Setting 0 = watchdog disabled
r3986[0...1]
Number of parameters
- - - - - U16 4
Number of parameters on the converter.
Index:
[0]
Read only
[1]
Read & write
r4000 - r4064
Reserved

Table of Contents