Options and spare parts
B.1 Options
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
395
Fixing to FSA/FSAC/FSAD
Loosen the PE screw and slide the shielding plate
from below, then retighten the screw to 1.8 Nm (toler-
ance: ± 10%).
Clamp the heatsink between the shielding plate and
the cabinet panel and tighten the screws and nuts to 1.8
Nm (tolerance: ± 10%).
Fold the cable shield clamp to suit the cable diameter
during converter installation.
Fixing to FSB/FSC/FSD/FSE
Clamp the heatsink between the clip and the shielding
plate, and tighten the screw to 1.8 Nm (tolerance: ± 10%).
Fold the cable shield clamp to suit the cable diameter
during converter installation.
If the converter applies push-through mounting mode:
Fixing to FSB/FSC/FSD/FSE
Note that the clips are not required in this case.
Clamp the heatsink between the shielding plate and
the cabinet panel, and use two mating nuts instead of the
clips to tighten the screws (M4 screws if frame size B or
M5 screws if frame size C or D) from the back of the cab-
inet panel. Screw tightening toque: M4 = 1.8 Nm ± 10%;
M5 = 2.5 Nm ± 10%
Fold the cable shield clamp to suit the cable diameter
during converter installation.