Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
67
Setting connection macros
Connection macro Cn001 - BOP as the only control source
Connection macro settings:
Parameter
Description
Factory default
Default for Cn001
Remarks
P0700[0]
Selection of command source
1
1
BOP
P1000[0]
Selection of frequency
1
1
BOP MOP
P0731[0]
BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Converter fault active
P0771[0]
CI: Analog output
21
21
Actual frequency
P0810[0]
BI: CDS bit 0 (Hand/Auto)
0
0
Hand mode