Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
69
Parameter
Description
Factory default
Default for Cn002
Remarks
P0771[0]
CI: Analog output
21
21
Actual frequency
P0731[0]
BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Converter fault active
Connection macro Cn003 - Fixed speeds
Three fixed speeds with ON/OFF1
If more than one fixed frequency is selected at the same time, the selected frequencies are
summed, that is, FF1 + FF2 + FF3.
Connection macro settings:
Parameter
Description
Factory default
Default for Cn003
Remarks
P0700[0]
Selection of command source
1
2
Terminal as command source
P1000[0]
Selection of frequency
1
3
Fixed frequency
P0701[0]
Function of digital input 1
0
1
ON/OFF
P0702[0]
Function of digital input 2
0
15
Fixed speed bit 0
P0703[0]
Function of digital input 3
9
16
Fixed speed bit 1
P0704[0]
Function of digital input 4
15
17
Fixed speed bit 2
P1016[0]
Fixed frequency mode
1
1
Direct selection mode
P1020[0]
BI: Fixed frequency selection bit 0
722.3
722.1
DI2
P1021[0]
BI: Fixed frequency selection bit 1
722.4
722.2
DI3
P1022[0]
BI: Fixed frequency selection bit 2
722.5
722.3
DI4
P1001[0]
Fixed frequency 1
10
10
Speed low
P1002[0]
Fixed frequency 2
15
15
Speed middle
P1003[0]
Fixed frequency 3
25
25
Speed high
P0771[0]
CI: Analog output
21
21
Actual frequency
P0731[0]
BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Converter fault active