Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
71
Connection macro Cn005 - Analog input and fixed frequency
The analog input works as an additional setpoint.
If digital input 2 and digital input 3 are active together, the selected frequencies are summed,
that is, FF1 + FF2.
Function diagram
When the fixed speed is selected, the additional setpoint channel from the analog is
disabled. If there is no fixed speed setpoint, the setpoint channel connects to the analog
input.
Connection macro settings:
Parameter
Description
Factory default
Default for Cn005
Remarks
P0700[0]
Selection of command source
1
2
Terminals as command source
P1000[0]
Selection of frequency
1
23
Fixed frequency + analog setpoint 1
P0701[0]
Function of digital input 1
0
1
ON/OFF
P0702[0]
Function of digital input 2
0
15
Fixed speed bit 0
P0703[0]
Function of digital input 3
9
16
Fixed speed bit 1
P0704[0]
Function of digital input 4
15
9
Fault acknowledgement
P1016[0]
Fixed frequency mode
1
1
Direct selection mode
P1020[0]
BI: Fixed frequency selection bit 0
722.3
722.1
DI2
P1021[0]
BI:
Fixed frequency selection bit 1
722.4
722.2
DI3