Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
72 Operating Instructions, 10/2019, A5E34559884-012
Parameter
Description
Factory default
Default for Cn005
Remarks
P1001[0]
Fixed frequency 1
10
10
Fixed speed 1
P1002[0]
Fixed frequency 2
15
15
Fixed speed 2
P1074[0]
BI: Disable additional setpoint
0
1025.0
FF disables the additional setpoint
P0771[0]
CI: Analog output
21
21
Actual frequency
P0731[0]
BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Converter fault active
Connection macro Cn006 - External push button control
Note that the command sources are pulse signals.
Connection macro settings:
Parameter
Description
Factory default
Default for Cn006
Remarks
P0700[0]
Selection of command source
1
2
Terminals as command source
P1000[0]
Selection of frequency
1
1
MOP as setpoint
P0701[0]
Function of digital input 1
0
2
OFF1/hold
P0702[0]
Function of digital input 2
0
1
ON pulse
P0703[0]
Function of digital input 3
9
13
MOP up pulse
P0704[0]
Function of digital input 4
15
14
MOP down pulse
P0727[0] Selection of 2/3-wire method 0 3 3-wire
ON pulse + OFF1/hold + Reverse
P0771[0]
CI: Analog output
21
21
Actual frequency
P0731[0]
BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Converter fault active
P1040[0]
Setpoint of the MOP
5
0
Initial frequency
P1047[0] MOP ramp-up time of the RFG 10 10 Ramp-up time from zero to maxi-
mum frequency
P1048[0] MOP ramp-down time of the RFG 10 10 Ramp-down time from maximum
frequency to zero