Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
74 Operating Instructions, 10/2019, A5E34559884-012
Connection macro Cn008 - PID control with analog reference
Note
If a negative setpoint for the PID control is de
sired, change the setpoint and feedback wiring
as needed.
When you switch to Hand mode from PID control mode, P2200 becomes 0 to disable the
PID control. When you switch it back to Auto mode, P2200 becomes 1 to enable the PID
control again.
Connection macro settings:
Parameter
Description
Factory default
Default for Cn008
Remarks
P0700[0]
Selection of command source
1
2
Terminals as command source
P0701[0]
Function of digital input 1
0
1
ON/OFF
P0703[0]
Function of digital input 3
9
9
Fault acknowledgement
P2200[0]
BI: Enable PID controller
0
1
Enable PID
P2253[0]
CI: PID setpoint
0
755.0
PID setpoint = AI1
P2264[0]
CI: PID feedback
755.0
755.1
PID feedback = AI2
P0756[1]
Type of analog input
0
2
AI2, 0 mA to 20 mA
P0771[0]
CI: Analog output
21
21
Actual frequency
P0731[0]
BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Converter fault active