Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
82 Operating Instructions, 10/2019, A5E34559884-012
Parameters for
conventional
quick commis-
sioning
Parameters for
estimated quick
commissioning
P0305[0] ● - Rated motor current [A] Range: 0.01 to 10000
The input of rating plate data must correspond with the
wiring of the motor (star/delta).
P0307[0] ● - Rated motor power
[kW/hp]
Range: 0.01 to 2000.0
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
P0308[0] ● - Rated motor power factor
(cosφ)
Range: 0.000 to 1.000
This parameter is visible only when P0100 = 0 or 2.
P0309[0] ● - Rated motor efficiency [%] Range: 0.0 to 99.9
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
P0310[0] ● - Rated motor frequency
Range: 12.00 to 550.00
P0335[0] P0335[0] Motor cooling Set according to the actual motor cooling method
= 0: Self-cooled (factory default)
= 1: Force-cooled
= 2: Self-cooled and internal fan
= 3: Force-cooled and internal fan
P0640[0] P0640[0] Motor overload factor [%] Range: 10.0 to 400.0 (factory default: 150.0)
The parameter defines motor overload current limit rela-
tive to P0305 (rated motor current).
P0700[0] P0700[0] Selection of command
source
= 0: Factory default setting
= 1: Operator panel (factory default)
= 2: Terminal
P1000[0] P1000[0] Selection of frequency
setpoint
Range: 0 to 77 (factory default: 1)
= 0: No main setpoint
= 1: MOP setpoint
= 2: Analog setpoint 1
= 3: Fixed frequency
= 5: USS/MODBUS on RS485
= 7: Analog setpoint 2
For additional settings, see Chapter "Parameter list