Troubleshooting Procedures
3.19 Parameter 6.SCUR
PS2 Troubleshooting Guide
Service Manual, 03/2017, A5E36661550-AA
33
Figure 3-3 Linear Application
Linear Applications, see Initialization Procedure (Page 50)
3.19
Parameter 6.SCUR
Default setting is: "4 mA".
From AUT or MAN mode, press
button for 5 seconds.
Now observe the parameter name in the lower right corner.
Continue to press the
button until "SCUR" parameter is reached.
If it says "0 mA", press the
button to change this to "4 mA".
To return to Automatic mode, press and hold the
button for 5 seconds.
The unit will now be in Manual mode.
Press the
button one time to return to Automatic mode.
3.20
Re-Initialization Positioner
See Initialization Procedure (Page 50)

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h

Related product manuals