EasyManuals Logo

Siemens SIPART PS2 Service Manual

Siemens SIPART PS2
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
Appendix A
A.4 SIPART PS2 Valve Positioner Fail-Safe Positions
PS2 Troubleshooting Guide
62 Service Manual, 03/2017, A5E36661550-AA
Adjust slip clutch until number in display is within a range of: 48-52.
Figure A-2 Slip Clutch
Move valve so the numerical number decreases, either by pressing the or button.
Once the numerical value begins to decrease, keep button pressed to go to end-stop
position.
If numerical value goes through zero before reaching end-stop position, see
"Determine Proper Slide Bar Setting" procedure above.
Once at end-stop position adjust slip clutch so numerical value is within the following
numerical range: 5.8 to 6.8.
Using other push button drive valve to other end-stop position.
Numerical value should be less than 95, if not:
○ See "Determine Proper Slide Bar Setting" section above, or…
○ For linear valves, there can be too much mechanical travel on feedback arm.
Mechanical feedback travel should not exceed 100° rotation. If necessary secure
feedback pin further away from positioner’s input shaft or…
○ Actuator end-stops are set too wide, narrow actuator end-stop travel.
Unit is now ready for intiialization procedure. See Initialization Procedure.
A.4
SIPART PS2 Valve Positioner Fail-Safe Positions
When designing a process loop containing a valve and valve positioner, it is wise to consider
the position the valve should go to, i. e., the valve’s fail-safe position, in response to each
potential system failure. Often valve position during a system failure is not considered until
an actual failure occurs and the valve goes to an unexpected position. This can result in a
hazardous situation for plant personnel, damage to process equipment, or loss of product or
product constituents. Valve fail-safe position is implemented when piping a positioner to a
valve actuator.
Figure A-3 Reaction to failure of auxiliary powers
below shows the resulting actuator/valve
positions for various positioner-to-actuator piping connections and with loss of input signal
and/or supply air.

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h

Related product manuals