Appendix A
A.2 Initialization Procedure
PS2 Troubleshooting Guide
50 Service Manual, 03/2017, A5E36661550-AA
Set Transmission Ratio Selector (Slide Bar) according to the actuator's requirements.
Rotary
- Always 90°
Linear
less than 25 mm/1 inch 33°
Linear
greater than 25 mm/1 inch 90°
Proceed to adjust the gear latch to match the Transmission Ratio/Slide Bar.
A.2
Initialization Procedure
PS2 Positioner Calibration Procedure Rotary Linear Actuators
6DR5x1, 6DR5x2 (x = 0,1,2,3,5,6)
Verify the positioner is mounted correctly using factory couplings to ensure there is NO
BACKLASH between the positioner input shaft and the actuator output shaft. Check that
there is sufficient supply pressure to operate the actuator/valve configuration. This is critical
on spring return (single-acting) actuators. Insufficient air pressure will result in a calibration
error.
Confirm a 4 20 mA source is properly connected to the 2-wire positioner (x = 0 or 1),
or a 2-, 3- or 4-wire positioner (x = 2 or 3).
Connect a 24 VDC power supply for Profibus
(6DR55) or Foundation Fieldbus (6DR56) for bench top configuration. For complete details
on the above, please refer to the "Operating Instructions" manual supplied on the CD in the
positioner’s box. Under the Navigation tab, expand "electropneumatic positioners" and then
"SIPART PS2". Choose input source, i.e. 4-20 mA = "SIPART PS2 with and without HART.

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h