Appendix A
A.4 SIPART PS2 Valve Positioner Fail-Safe Positions
PS2 Troubleshooting Guide
Service Manual, 03/2017, A5E36661550-AA
63
SIPART PS2 Attributes
Separate models for single and double-acting applications.
Single-acting units vent output pressure upon loss of control signal and supply air.
Double-acting units: Y1 goes to maximum pressure & Y2 vents upon loss of control
signal.
Double-acting units block and trap output pressure in actuator upon loss of supply air.
Double-acting units: If venting an output port upon loss of air is desired, we offer a venting
gauge block to exhaust output port Y2.
Units with "F01" in the model code (Fail-in-Place) block and trap output pressure in
actuator upon loss of control signal. See
Figure A-4 Reaction to failure of auxiliary power
with fail in place
below.
Part Number
Description
6DR4004-2RF
Venting gauge block, Aluminum
A6X30005128 Venting gauge block, SST
Digital Communications
In addition to electric and pneumatic power, digital positioners require continuous digital
communication for proper operation. Both Foundation Fieldbus and Profibus power and
communicate with the PS2 using a single pair of wires. Therefore, it is possible to lose digital
communication and have device power.
The following Profibus and Foundation Fieldbus parameters will help you predict actuator
position upon loss of digital fieldbus communications only; for loss of electrical and
pneumatic power, see
Figure A-3 Reaction to failure of auxiliary powers
and
Figure A-4
Reaction to failure of auxiliary power with fail in place
below.
The following overview diagram shows the pneumatic connection variations for different
acutator types, regulating action and safety position after an auxiliary supply failure.
CAUTION
Before working on the control valve
Note that before working on the control valve, you must first move it to the safety position.
Make sure that the control valve has reached the safety position. If you only interrupt the
pneumatic auxiliary power supply to the positioner, the safety position may in some cases
only be attained after a certain delay period.

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h