A.4 SIPART PS2 Valve Positioner Fail-Safe Positions
PS2 Troubleshooting Guide
66 Service Manual, 03/2017, A5E36661550-AA
FSAC
, Fail Safe factory: As per power failure modes indicated in above table:
Single-acting models - Y1 exhaust to zero pressure.
Double-acting models- Y2 exhaust to zero and Y1 increases to supply pressure.
FSTI
, Fail Safe Time: Elapsed time after communication loss before going to safety position.
FSVL
, Fail Safe Valve: Safety position upon communication loss, pre-requisite: FSTY=FSVL
Foundation Fieldbus Parameters
The following Analog Output Block safety parameters are accessible only via Foundation
Fieldbus configuration software, i. e.: National Configurator.
IO_OPTS:
Faultstate Type (bit 6) = 0 or unchecked will hold last position upon loss of communication.
Faultstate Type (bit 6) = 1 or checked will position actuator as per "FSTATE_VAL"
parameter.
FSTATE_VAL:
Desired actuator position upon loss of digital communication, Faultstate Type must = 1.
FSTATE_TIME:
Elapsed time after communication loss before going to safety position.
Safety Shutdown
Profibus only positioners are equipped with an additional input to drive an actuator to the
PS2’s factory safety position; see
Figure A-3 Reaction to failure of auxiliary powers
above.
See
Figure A-4 Reaction to failure of auxiliary power with fail in place
above if unit has Fail-
in-Place option.
To activate this feature, change position of ‘Shut Down’ jumper located underneath
secondary cover.
Once enabled, 24Vdc must be maintain on terminals 81 and 82. Otherwise, the positioner
will drive the actuator as shown in
Figure A-3 Reaction to failure of auxiliary powers
above.
See
Figure A-4 Reaction to failure of auxiliary power with fail in place
above if unit has Fail-
in-Place option.
Single-acting models - Y1 exhausts to zero pressure.
Double-acting models- Y2 exhausts to zero and Y1 increases to supply pressure.
Once enabled, this feature will override any soft parameter settings as mentioned above.

Table of Contents

Other manuals for Siemens SIPART PS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 and is the answer not in the manual?

Siemens SIPART PS2 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
Communication ProtocolsHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Pressure0 to 100% of supply pressure
Hazardous Area CertificationATEX, IECEx, FM, CSA
TypeElectropneumatic
Input Signal4-20 mA
Rotation Angle30° to 90°
Operating Temperature-40°C to +80°C
MountingLinear and rotary actuators
Air ConsumptionTypically less than 0.1 kg/h