Modbus register map
7SJ61/62/63 6MD63 - Modbus
C53000-L1840-C001-01
6-17
Register
address
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10247 59-1 TRIP 1 = 59 TRIP 6570
10248
-
10256
reserved
4
–
6.4.9 Register addresses 10257 to 10278: Sensitive ground fault protection
Register
address
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10257 >BLOCK 64 1 = >BLOCK 64 1201
10258 >BLOCK 50Ns-2 1 = >BLOCK 50Ns-2 1202
10259 >BLOCK 50Ns-1 1 = >BLOCK 50Ns-1 1203
10260 >BLOCK 51Ns 1 = >BLOCK 51Ns 1204
10261 >BLK 50Ns/67Ns 1 = >BLK 50Ns/67Ns 1207
10262 50Ns/67Ns OFF 1 = 50Ns/67Ns is switched OFF 1211
10263 50Ns/67Ns ACT 1 = 50Ns/67Ns is ACTIVE 1212
10264 64 Pickup 1 = 64 displacement voltage pick up 1215
10265 64 TRIP 1 = 64 displacement voltage element TRIP 1217
10266 50Ns-2 Pickup 1 = 50Ns-2 Pickup 1221
10267 50Ns-2 TRIP 1 = 50Ns-2 TRIP 1223
10268 50Ns-1 Pickup 1 = 50Ns-1 Pickup 1224
10269 50Ns-1 TRIP 1 = 50Ns-1 TRIP 1226
10270 51Ns Pickup 1 = 51Ns picked up 1227
10271 51Ns TRIP 1 = 51Ns TRIP 1229
10272 Sens. Gnd block 1 = Sensitive Ground fault detection BLOCKED 1230
10273 Sens.Gnd Pickup 1 = Sensitive Ground fault pick up 1271
10274 Sens. Gnd Ph A 1 = Sensitive Ground fault picked up in Ph A 1272
10275 Sens. Gnd Ph B 1 = Sensitive Ground fault picked up in Ph B 1273
10276 Sens. Gnd Ph C 1 = Sensitive Ground fault picked up in Ph C 1274
10277 SensGnd Forward 1 = Sensitive Gnd fault in forward direction 1276
10278 SensGnd Reverse 1 = Sensitive Gnd fault in reverse direction 1277
10279 SensGnd undef. 1 = Sensitive Gnd fault direction undefined 1278
10280
-
10288
reserved
4
–