Modbus register map
7SJ61/62/63 6MD63 – Modbus
C53000-L1840-C001-01
6-28
6.6.3 Register addresses 40201 to 40215: Metered measurands
•
Data type definition ref. to chap. 5.4,
•
Registers are write-protected
7
.
Scaling
The scaling of the metered measurands, which are derived from
measured values, refers to:
60000 impulses per hour for V = V
prim
and I = I
prim
V
prim
= P
RIMARY
O
PERATING
V
OLTAGE
(parameter address = 1101)
I
prim
= P
RIMARY
O
PERATING
C
URRENT
(parameter address = 1102)
Example
In the parameter set is configured:
I
prim
= 100 A und V
prim
= 12 kV,
60000 impulses correspond so that:
1 h * 100 A * 12 kV *
3
= 2078.46 kWh
Note
The type of the update (cyclic, with or without deletion) and the update
interval must be programmed for the metered measurands (except for
the operating hours meter) with the parameterization software DIGSI.
Register
address
Designation of the
SIPROTEC objects
Comments
Scaling
(2
31
-1 of the unsigned long
value corresponds to...)
Internal
object
no.
40201
–
40202
Wp(puls) = Pulsed Energy Wp (active)
(metering impulses at binary input)
2
31
-1 impulses 888
40203
–
40204
Wq(puls) = Pulsed Energy Wq (reactive)
(metering impulses at binary input)
2
31
-1 impulses 889
40205
–
40206
WpForward= Wp Forward
(
metered measurand derived from
measured value
)
2
31
-1 impulses 924
40207
–
40208
WqForward= Wq Forward
(
metered measurand derived from
measured value
)
2
31
-1 impulses 925
40209
–
40210
WpReverse = Wp Reverse
(
metered measurand derived from
measured value
)
2
31
-1 impulses 928
40211
–
40212
WqReverse = Wq Reverse
(
metered measurand derived fom
measured value
)
2
31
-1 impulses 929
40213
–
40214
Op.Hours= Counter of operating hours of the
primary equipment
2
31
-1 hours 1020