Modbus register map
7SJ61/62/63 6MD63 - Modbus
C53000-L1840-C001-01
6-25
Register
address
Designation of the
SIPROTEC objects
Comments
Scaling
(32767 corresponds to ...)
Internal
object no.
30023 V2 = V2 (negative sequence) 1: 327.67 kV
2: 32.767 kV
3: 32.767 kV
630
30024 3Vo = 3Vo (zero sequence) 1: 327.67 kV
2: 32.767 kV
3: 32.767 kV
832
30025 <Theta> Rotor Temperature of rotor
327.67 %
805
30026 <Theta> Stator Temperature of stator
327.67 %
806
30027 Td1= Transducer 1
32.767 mA
996
30028 Td2= Transducer 2
32.767 mA
997