EasyManuals Logo
Home>Siemens>Control Unit>SIPROTEC PROFINET IO

Siemens SIPROTEC PROFINET IO User Manual

Siemens SIPROTEC PROFINET IO
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
2 PROFINET IO in SIPROTEC
2.6 Event List
43SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
2.6.2 Output Direction
The following structure corresponds to the IO module event list, data in output direction. The structure is not
used for process alarms.
Figure 2-20 Structure of the Event List, Output Direction (ACK)
Message-Block Number
The message-block number in the Control_O byte serves for reception acknowledgement and analysis of the
message block. After having analyzed the message blocks, the PROFINET IO controller copies the message-
block number of the Control_I byte of the input telegram to the Control_O byte of the output telegram.
The SIPROTEC device repeats the respective message block so often until the IO controller correctly mirrors
back the message-block number of the Control_I byte into the Control_O byte.
Control _O byte
Reserved = 0
Control _O byte
7 6 5 4 3 2 1 0
Message-block
number
Reserved = 0
Bit position
Meaning
com_profinet-io_profile_us.book Page 43 Friday, August 17, 2012 1:40 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC PROFINET IO and is the answer not in the manual?

Siemens SIPROTEC PROFINET IO Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC PROFINET IO
CategoryControl Unit
LanguageEnglish

Related product manuals