4 PROFINET IO Diagnosis
4.2 PROFINET IO Error Indication in the SIPROTEC 4 Device
91SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
4.2 PROFINET IO Error Indication in the SIPROTEC 4 Device
Display in DIGSI
The indication SysIntErr. (error of the system interface) is used for the PROFINET IO error indication. In the
DIGSI configuration matrix, this indication is available in the Protocol menu.
Figure 4-4 Error Indication of the System Interface (DIGSI)
The following table contains the description of the error indication:
Table 4-1 Error Indication SysIntErr.
Error
indication
After restart ON OFF OFF ON
SysIntErr. = ON Change to OFF if the IO
controller is connected and cyclic
IO data are exchanged.
Change to ON if the IO controller
is not connected anymore or if no
cyclic data are exchanged any-
more.
com_profinet-io_profile_us.book Page 91 Friday, August 17, 2012 1:40 PM