Drive functions
5.4 Force control
Hydraulic Drive
162 System Manual, 04/2015, 6SL3097-4BA00-0BP1
5.4.1
Force limitation
Force limitation threshold (plus/minus) around the force of weight and weight force limiting.
If a pressure sensor is installed and connected for the pressures at A and B, the force
limitation in p1400 can be activated.
In the case that the value set in the parameters p1520 and p1521 plus the force due to
weight (p1532) may be exceeded or if there is a possibility that the force due to weight
(p1532) minus the value set in the parameters p1520 and p1521 is fallen below, then the
force controller ensures that the set cylinder force values are limited to the corresponding
values.
Since only the cylinder force is measured and controlled, it may be necessary to take into
account the force due to weight in parameter p1520 and the friction force in parameters
p1521 and p1532.
An additional force limitation value, with the same effect as p1520/p1521, can be entered
from the control, e.g. when traversing to the fixed stop. The lower of the two force limit
thresholds is then applied.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
p1400[0...n]
Closed
-loop control configuration
p1520[0...n]
CO: Force limit upper/motoring
p1521[0...n]
CO: Force limit lower/regenerative
p1532[0...n]
CO: Force offset, force limit
5.4.2
Stiction compensation
5.4.2.1
Stiction compensation using the force controller
If the pressures at A and B are sensed, then the stiction compensation using the force
controller can be activated (p1400.2=1).
Static force compensation using the force controller should not be activated if the cylinder is
required to hold a fluctuating force due to weight. In addition, the offset of the valve control
voltage and the piston must already have been calibrated. Parameters p1552 to p1556 can
be calibrated using the circularity test.
Preconditions
The following preconditions must be fulfilled to use stiction compensation with the force
controller:
Pressure sensors must be available for p
A
and p
B
The force controller must have already been commissioned.
External force (F
center
) does not change.

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals