Diagnosing and troubleshooting
9.4 Fault codes and corrective actions
SITRANS F Ultrasonic flowmeters FST030 (HART)
Operating Instructions, 08/2017, A5E35971532-AC
107
259
Standard density Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Lower alarm limit"
Only hydrocarbon
260
API gravity Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Upper alarm limit"
Only hydrocarbon
261
API gravity Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Upper warning limit"
Only hydrocarbon
262
API gravity Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Lower warning limit"
Only hydrocarbon
263
API gravity Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Lower alarm limit"
Only hydrocarbon
264
Standard API gravity Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Upper alarm limit"
Only hydrocarbon
265
Standard API gravity Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Upper warning limit"
Only hydrocarbon
266
Standard API gravity Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Lower warning limit"
Only hydrocarbon
267
Standard API gravity Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Lower alarm limit"
Only hydrocarbon