Diagnosing and troubleshooting
9.4 Fault codes and corrective actions
SITRANS F Ultrasonic flowmeters FST030 (HART)
96 Operating Instructions, 08/2017, A5E35971532-AC
ID/
Icons
Diagnostic
Action
Comment
134
Standard volume flow Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Lower warning limit'
Only hydrocarbon
135
Standard volume flow Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
Only hydrocarbon
136
Totalizer 1 Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
137
Totalizer 1 Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Upper warning limit'
138
Totalizer 1 Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Lower warning limit'
139
Totalizer 1 Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
140
Totalizer 2 Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
141
Totalizer 2 Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Upper warning limit'
142
Totalizer 2 Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Lower warning limit'