Diagnosing and troubleshooting
9.4 Fault codes and corrective actions
SITRANS F Ultrasonic flowmeters FST030 (HART)
Operating Instructions, 08/2017, A5E35971532-AC
95
105
Density Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Upper warning limit'
106
Density Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Lower warning limit'
107
Density Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
108
Medium temperature Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
109
Medium temperature Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Upper warning limit'
110
Medium temperature Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Lower warning limit'
111
Medium temperature Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
132
Standard volume flow Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
Only hydrocarbon
133
Standard volume flow Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter 'Upper warning limit'
Only hydrocarbon