Installing/Mounting
4.2 Determining a location
SITRANS F M MAG 3100
22 Operating Instructions, 06/2010, A5E03005599-01
4.2 Determining a location
NOTICE
The sensor must always be completely filled with liquid.
Figure 4-1 Correct installation with filled pipes
● Avoid the following installations
– Installation at the highest point in the pipe system
– Installation in vertical pipes with free outlet
– Wrong installation at high point
Figure 4-2 Correct installation at low point before outlet