Installing/Mounting
4.7 Installation with earthing flanges
SITRANS F M MAG 3100
Operating Instructions, 06/2010, A5E03005599-01
31
4.7 Installation with earthing flanges
CAUTION
Only sensors with PTFE or PFA liners
Installation with earthing flanges is only relevant for sensors with PTFE or PFA liners
Mount earthing flanges where necessary on non conductive pipes.
Installation with earthing flanges on sensors
with PTFE liner
Installation
with flat earthing ring on sensors
with PFA liner
NOTICE
Potential equalization
For potential equalization one earthing flange is sufficient even for bidirectional flow.
By unidirectional flow the earthing flange must be mounted on the inlet side.
Connect the earthing flanges to the sensor with the enclosed earthing straps.
Earthing strap connection on flat earthing
rings
Earthing
strap connection on type E earthing
rings